The glass gets the attention when people compare an energy efficient skylight, but on a flat roof the box underneath it matters just as much. Our energy efficient rooflights page covers the glazing side; this answer deals with the part that sits below the frame, and why an insulated rooflight upstand is the normal specification rather than an optional extra.
What the upstand is doing on a flat roof
A flat rooflight cannot sit directly on the deck. It needs a raised kerb so the roof's waterproofing can be turned up and dressed under the frame, clear of standing water. That kerb is a short, four-sided wall, and it pokes up through the insulated roof into the cold outside air. Whatever it is made of, heat inside the room can travel up through it to the outside.
If the kerb is solid timber with nothing lining it, that timber becomes a weak spot running all the way round the opening. The glazing unit above might be triple glazed with a low figure on its label, yet the ring of wood beneath it lets warmth bypass the glass entirely. The rooflight looks efficient on paper and feels cold at the edges in practice.
The rule: the upstand should carry insulation continuously from the roof build-up to the underside of the rooflight frame, with no gap at the corners or at the deck. The exception: some makers supply the rooflight and a matched insulated kerb as one tested unit, in which case the kerb is fitted as supplied and not altered on site.
How a sealed rooflight unit works and fails
- Outer and inner glass panes, with the outer pane facing the weather
- Low-emissivity coating on one inner face, reflecting heat back into the room
- Warm-edge spacer bar holding the panes apart, filled with desiccant to soak up trace moisture
- Primary seal against each pane, backed by the secondary seal around the edge
- Dry sealed cavity, the insulating layer between the panes
- Broken edge seal: moist air gets in and the desiccant becomes saturated
- Mist and droplets trapped between the panes; they cannot be wiped off and the sealed unit needs replacing
- Inset: condensation on the room-side face of the glass is a ventilation or humidity issue, not a failed unit
Factory kerb or lined timber kerb
There are two usual ways to get an insulated upstand, and each has its place depending on the roof and the product.
| Point | Factory insulated kerb | Timber kerb lined on site |
|---|---|---|
| What it is | A pre-formed kerb with an insulated core, made to suit a named rooflight | A kerb built from timber on the roof, then wrapped or lined with rigid insulation board |
| Where it suits | New flat roofs and rooflights sold with a matching kerb | Odd sizes, existing openings, or where the kerb height must match an older roof build-up |
| Thermal detail | Fixed by the maker and often covered by the declared unit figure | Depends on the board thickness and on closing every joint and corner |
| What to check | That the kerb matches the rooflight model and the roof covering | That insulation meets the roof insulation below and the frame above without a break |
Neither is wrong. What matters is that the insulation line is unbroken, and that the kerb height works with the waterproofing and with any insulation added when the roof was last recovered.
Why it shows up as condensation first
The first sign of an uninsulated upstand is rarely a heating bill. It is moisture. Warm, damp air from a kitchen or bathroom meets the chilled inner face of the kerb, and water beads on the lining or the reveal. Over a winter that brings stained plaster, black spotting in the corners, and paint that will not stay put. People often blame the glass, but the glass is fine; the cold surface is the box it sits on.
Lining the kerb moves that cold surface to the outside, so the room-side face stays near room temperature. Our guide to thermally broken frames and cold bridging at the upstand goes through the heat path in detail, and the answer on whether energy efficient rooflights reduce condensation sets out what better glazing can and cannot change on its own.
Part L and the declared U-value
A new or replacement rooflight is a controlled fitting under the Building Regulations, so its thermal performance has to meet Part L. Check what the published figure actually covers. Some makers quote the glazing centre, some the whole unit, and some the whole unit on their own insulated kerb. A good figure measured with a matched kerb only holds if that kerb, or an equivalent, is what goes on the roof.
For the headline number a new unit should reach, see what U-value a new rooflight should have. For replacing an existing skylight on an older extension, does a replacement rooflight have to meet Part L? answers the question directly. Where the work is notifiable, Everlight looks after the Building Control side as part of the job.
Swapping an old dome on an estate extension
Single-storey rear extensions on the 1970s and 1980s estates around Basingstoke, in places such as Brighton Hill, Lychpit or Oakridge, were often finished with a plastic dome on a plain timber kerb. When that dome comes off, the kerb underneath is exposed, and it is usually the moment to decide whether it stays, gets lined, or is replaced with an insulated kerb sized for the new rooflight.
- Look at the existing kerb. Its height, its condition and how the flat roof covering is dressed up it.
- Match it to the new unit. Confirm whether the chosen rooflight needs its own kerb or can sit on a lined timber one.
- Close the insulation line. Board to the kerb faces, joined at the corners, meeting the roof insulation and the frame.
- Dress the waterproofing. Turn the roof covering up the new or lined kerb and finish it under the frame.
- Finish the reveal inside. Line and decorate the inner face so it reads as part of the ceiling.
What decides the answer on your roof
The right upstand depends on the roof you have: how thick the existing insulation is, whether it sits above or below the deck, the covering, and the rooflight you want. That is why we survey before we quote, measuring the kerb and checking the build-up rather than guessing from a photo. The fitting then carries our 10-year workmanship guarantee.
If you have a cold, damp ring round a flat roof skylight or you are planning a new one, arrange a survey of the flat roof and we will tell you which kind of insulated upstand suits it.